Is Your Business Properly Protected by Your Fire Alarm System?

As a business owner in Galway, ensuring the safety of your employees, customers, and property is a top priority. A crucial aspect of this responsibility is having a comprehensive fire alarm system that meets the unique needs of your commercial premises. But how can you be sure that your current system provides the necessary coverage and protection?

At Pro Security, we specialise in designing, installing, and maintaining fire alarm systems tailored to the specific requirements of businesses in Galway and the surrounding areas. To help you assess your current system, we've compiled a checklist of key factors to consider:

Control Panel: Your commercial fire alarm system should have a control panel that operates and monitors all installed detectors and sounders. It should also include a backup battery to ensure uninterrupted operation in the event of a power failure.

Detection Coverage: The level of detection coverage required depends on your premises' size and layout. The categories range from L1 (detection throughout the entire premises) to L4 (detection on escape routes only).

Sounder Circuits: A minimum of two sounder circuits should be installed inside the building to ensure a backup in case one circuit fails. The number of sounders required depends on the internal layout and the type of sounders used.

Sounder Placement: Wall-mounted sounders should provide an output of 105 decibels (dBA) when set to high, while sounder bases may be slightly lower. Ensure that the sound level is at least 65 dBA above background noise throughout the premises, and 75 dBA in bedrooms to wake sleeping occupants.

Smoke Detector Spacing: Smoke detectors should provide coverage up to 100m² on a flat ceiling, with a maximum distance of 6m from any wall or obstruction and no more than 12m between detectors. Additional detectors may be necessary depending on the building's layout.

Heat Detector Spacing: Heat detectors should provide coverage up to 50m² on a flat ceiling, with a maximum distance of 5m from any wall or obstruction and no more than 10m between detectors. Additional detectors may be required based on the building's layout.

Detector Mounting Heights: Point-type smoke detectors should not be mounted on ceilings exceeding 10.5m, while A1R heat detectors should not exceed 9m, and other heat detectors should not exceed 7.5m.

If you're unsure whether your current fire alarm system meets these criteria or provides adequate protection for your business premises, it's time to take action. Contact Pro Security today to schedule a comprehensive assessment of your fire safety needs. Our experienced team will work closely with you to design a system that ensures the safety of your employees, customers, and property, giving you peace of mind and helping you stay compliant with local regulations.

Don't wait until it's too late – prioritise the safety of your business premises by ensuring your fire alarm system provides the coverage and protection you need. Get in touch with Pro Security now to discuss your requirements and learn how we can help safeguard your business.